Galaxy Power System 2436 Specifications (continued)
Mechanical
Cabinet
Full Height
Nominal Cabinet Dimensions
(H x W x D)
2100 H x 600 W x 600 D mm
(82.6 H x 23.6 W x 23.6 D in.)
Units Per Initial Cabinet
Full Height
Rectifiers
1 -
36
Controller
1
Battery Disconnect Modules
0 - 1
DC Distribution
Maximum discharge is 1600 amps per cabinet. No distribution panels can be
installed in a rectifier only cabinet, as many distribution panels as will fit can be
installed in other cabinets.
Units Per Supplemental Cabinet
Rectifiers
1 -
36
Battery Disconnect Modules
0 - 1
DC Distribution
Maximum discharge is 1600 amps per cabinet. No distribution panels can be
installed in a rectifier only cabinet, as many distribution panels as will fit can be
installed in other cabinets.
Environmental
Operating Ambient
Temperature
NE100AC24ATEZ
-40°C to +75°C
Altitude
-50 to 4000 meters
Note: For altitudes between 1500 and 4000 meters, derate the maximum
temperature by 0.656°C per 100 meters.
Humidity
5% to 95% non-condensing
Radiated and Conducted
Emissions
EN50082-1, EN50082-2, EN50081, EN61000
Electromagnetic Immunity
Level B
Earthquake Rating
Zone 4, upper floors
Standards Compliance
Agency Approvals
CE Marked, UL
Underwriters Laboratories (UL) Listed per Subject Letter 1801, DC Power
Distribution Centers for Telecommunications Equipment