GE Industrial Solutions GPS2436 User Manual
Page 73

Galaxy Power System GPS2436
Issue 1 August 2012
73
Contactor 1-3
Type
This setting identifies the type of contactor,
BATTERY, LOAD or NONE that has been
installed in the plant. Be sure that the wiring
for the contactor being configured matches
the type chosen here. For standard GPS
configurations using BIC cards, Contactor 1 is
wired to and controls all BATTERY contactors
in the plant. Contactors 2 and 3 are wired to
and control only LOAD contactors. To toggle
between the various contactor types, move
the cursor to one of the fields and use the
<+> or <-> key to select the desired type.
Press
Disconnect
This setting configures the plant voltage at
which the contactor will disconnect from the
bus. Use the <+> or <-> key to adjust the
voltage to the desired level. Press
to save the change.
Reconnect
This setting configures the plant voltage at
which the contactor will reconnect to the
bus. To prevent the contactor from re-
operating when battery voltage increases
due to load removal, a voltage several volts
higher than the disconnect voltage is
recommended. Use the <+> or <-> key to
adjust the voltage to the desired level. Press