2 bus bars interconnection, Bus bars interconnection – GE Industrial Solutions SG Series 750 T12 UL S2 Installation Guide User Manual
Page 21

Modifications reserved
Page 21/49
OPM_SGS_ISG_M75_M75_2US_V010.doc
Installation Guide SG Series 750 UL S2 & SG Series 750 T12 UL S2
3.7.2 Bus bars interconnection
WARNING !
All the inter cabinet wiring must be performed by QUALIFIED SERVICE PERSONNEL
only.
Inverter cabinet
Rectifier cabinet
8
9
4
3
2
1
7
6
5
10
SGS_750_S2_UPS connection cabinets_GE_01US
Fig. 3.7.2-1 Bus bars interconnections
Connection
Description of connection
Type (medium of connection)
Connection Type
(See Fig. 3.7.1-2)
1
Interconnection Bypass Line 1
1 Bus bar of size 40 x 10mm
Type 1
2
Interconnection Bypass Line 2
1 Bus bar of size 40 x 10mm
Type 1
3
Interconnection Bypass Line 3
1 Bus bar of size 40 x 10mm
Type 1
4
Interconnection for Inverter
output Line 1
1 Bus bar of size 40 x 10mm
Type 1
5
Interconnection for Inverter
output Line 2
1 Bus bar of size 40 x 10mm
Type 1
6
Interconnection for Inverter
output Line 3
1 Bus bar of size 40 x 10mm
Type 1
7
Neutral
1 Bus bar of size 80 x 10mm
Type 2
8
Positive DC bus bar
2 Flexi bars of size 5 x 40mm
Type 3
9
Negative DC bus bar
2 Flexi bars of size 5 x 40mm
Type 3
10
Inter cabinet Earthing
3 Flexi bars of size 4 x 32mm
Type 4