Mains Supply 3 x 525- 600 VAC
P560
P670
P750
P850
P1M0
Typical Shaft output at
550 V [kW]
560
670
750
850
1000
Typical Shaft output at
575 V [HP]
750
950
1050
1150
1350
Unit Size IP21, 54 with-
out/ with options cabi-
net
61/ 63
61/ 63
61/ 63
62/ 64
62/ 64
Output current
Continuous
(at 550 V) [A]
763
889
988
1108
1317
Intermittent (60 sec
overload)
(at 550 V) [A]
839
978
1087
1219
1449
Continuous
(at 575 V) [A]
730
850
945
1060
1260
Intermittent (60 sec
overload)
(at 575 V) [A]
803
935
1040
1166
1386
Continuous KVA
(at 550 V) [KVA]
727
847
941
1056
1255
Continuous KVA
(at 575 V) [KVA]
727
847
941
1056
1255
Max. input current
Continuous
(at 550 V ) [A]
743
866
962
1079
1282
Continuous
(at 575 V) [A]
711
828
920
1032
1227
Max. cable size,motor
[mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
12x150
(12x300 mcm)
Max. cable size,mains
[mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size, load-
sharing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake
[mm
2
(AWG
2)
)
4x185
(4x350 mcm)
6x185
(6x350 mcm)
Max. external pre-fuses
[A]
1
1600
2000
Estimated power loss
at rated max. load [W]
4)
Weight,
Unit Size IP21, IP 54 [kg]
1004/ 1299
1004/ 1299
1004/ 1299
1246/ 1541
1246/ 1541
Weight, Rectifier Module
[kg]
102
102
102
136
136
Weight, Inverter Module
[kg]
102
102
136
102
102
Efficiency
4)
0.98
Output frequency
0-500 Hz
Heatsink overtemp. trip
85 °C
Power card ambient trip
68 °C
1) For type of fuse see section Fuses.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the frequency converter
and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
Keypad and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses. (Though typical
only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
AF-600 FP High Power Operating Instructions
159