Af-600 fp high power operating instructions – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual
Page 155

Mains Supply 3 x 380 - 480 VAC
P110
P132
P160
P200
P250
Typical Shaft output at
400 V [kW]
110
132
160
200
250
Typical Shaft output at
460 V [HP]
150
200
250
300
350
Unit Size IP21
41
41
42
42
42
Unit Size IP54
41
41
42
42
42
Unit Size IP00
43
43
44
44
44
Output current
Continuous
(at 400 V) [A]
212
260
315
395
480
Intermittent (60 sec
overload)
(at 400 V) [A]
233
286
347
435
528
Continuous
(at 460 V) [A]
190
240
302
361
443
Intermittent (60 sec
overload)
(at 460 V) [A]
209
264
332
397
487
Continuous KVA
(at 400 V) [KVA]
147
180
218
274
333
Continuous KVA
(at 460 V) [KVA]
151
191
241
288
353
Max. input current
Continuous
(at 400 V ) [A]
204
251
304
381
463
Continuous
(at 460 V) [A]
183
231
291
348
427
Max. cable size, mains
motor, brake and load
share [mm
2
(AWG
2)
)]
2 x 70
(2 x 2/0)
2 x 70
(2 x 2/0)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
Max. external pre-fuses
[A]
1
300
350
400
500
600
Estimated power loss
at rated max. load [W]
4)
3234
3782
4213
5119
5893
Weight,
Unit Size IP21, IP 54 [kg]
96
104
125
136
151
Weight,
Unit Size IP00 [kg]
82
91
112
123
138
Efficiency
4)
0.98
Output frequency
0 - 800 Hz
Heatsink overtemp. trip
85 °C
90 °C
105 °C
105 °C
115 °C
Power card ambient trip
60 °C
AF-600 FP High Power Operating Instructions