Par. c-40 semi-auto jump freq set-up, Par. c-30 frequency command 2, Af-600 fp high power operating instructions – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual
Page 100

NB!
The decel ramp time is automatically adjusted to avoid tripping of the frequency converter.
C-05 Multi-step Frequency 1 - 8
Array [8]
Range:
Function:
0.00 %*
[-100.00 - 100.00 %]
Enter up to eight different preset references (0-7) in this parameter, using array programming. The preset
reference is stated as a percentage of the value Ref
MAX
(par. F-53 Maximum Reference, for closed loop
see par. CL-14 Maximum Reference/Feedb.). When using preset references, select Preset ref. bit 0 / 1 / 2
[16], [17] or [18] for the corresponding digital inputs in parameter group E-## Digital Inputs.
C-30 Frequency Command 2
Option:
Function:
Select the reference input to be used for the second reference signal. par. F-01 Frequency Setting 1, par.
C-30 Frequency Command 2 and par. C-34 Frequency Command 3 define up to three different reference
signals. The sum of these reference signals defines the actual reference.
This parameter cannot be adjusted while the motor is running.
[0]
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20] *
Digital Potentiometer
[21]
Analog input X30/11
(OPCGPIO)
[22]
Analog input X30/12
(OPCGPIO)
[23]
Analog Input X42/1
(OPCAIO)
[24]
Analog Input X42/3
(OPCAIO)
[25]
Analog Input X42/5
(OPCAIO)
[30]
Ext. Closed Loop 1
[31]
Ext. Closed Loop 2
[32]
Ext. Closed Loop 3
C-40 Semi-Auto Jump Freq Set-up
Option:
Function:
[0] *
Off
No function
[1]
Enabled
Starts the Semi-Automatic Bypass set-up and continue with the procedure described above.
AF-600 FP High Power Operating Instructions
98