l  Alarm  at  battery  mode:  If  disabled,  UPS  will  not  alarm  when  it’s  working  at 

battery mode. Vice versa. 

l  Auto  reboot:  If  enabled,  UPS  will  auto  recover  when  AC  is  recovering.  Vice 

versa. 

l  Bypass when UPS is off: If enabled, AC will directly provide power to connected 

devices when UPS is off. Vice versa. 

l  Converter mode: If enabled, the UPS will operate in converter mode. Vice versa. 

l  ECO mode: If enabled, the UPS will operate in ECO mode when input voltage is 

within acceptable range. Vice versa. 

l  Battery  open  status  check:  If  enabled,  the  monitored  UPS  will  check  if  the 

battery connection ok or not when UPS is turned on. 

l  Cold  start:  If  disabled,  the  UPS  can  be  turned  on  only  when  AC  is  normally 

connected to UPS. Vice versa. 

l  Bypass not allowed: If enabled, the UPS will not transfer to bypass mode under 

any conditions.  If disabled, the UPS will be allowed to transfer to bypass mode 

according to UPS internal setting. 

l  Battery deep­discharge protection: If enabled, the monitored UPS shutdown in 

accordance with the condition of battery and load on battery mode to protect 

battery. Vice versa. 

l  Site  fault  detection:  If  enabled,  the  monitored  UPS  will beep  when  the  input 

neutral and hot wires are reversed. Vice versa. 

l  P1  Programmable  outlet  control  (battery  mode):  If  enabled,  when  UPS  is 

running at battery mode, it will cut off P1 outlets after backup setting time arrive. 

If disabled, UPS will provide continuous power to P1 outlets until the battery is 

running out. 

l  Outlet setting: Users can set limited backup time for P1 outlets when UPS is on 

battery mode. 

l  Battery numbers setting: 

Ø 

Numbers in parallel: set battery numbers in parallel. 

l  Voltage  and  frequency  range  for  bypass  mode:  Set  acceptable  voltage  and