beautypg.com

4 technical data – VEGA VEGAMET 514… D User Manual

Page 7

background image

VEGAMET 514… D

7

1.4 Technical data

Power supply

Operating voltage

U

nenn

= 24 V AC (20 … 53 V), 50/60 Hz
= 24 V DC (20 … 72 V)

Power consumption

- VEGAMET 514 D

appr. 7 VA or appr. 5 W

- VEGAMET 514 VD

appr. 17 VA or appr. 12 W

Fuse

630 mA slow-blow

Measuring data input VEGAMET 514 D

Number

1 input

Kind of input

active two-wire input, analog

Range

4 … 20 mA
hydrostatic pressure transmitters

Voltage

at 4 mA appr. 18 V DC, at 20 mA appr. 15 V DC

Current limitation

at appr. 26 mA, shortcircuit proof

Detection-line interruption

< 2 mA

Detection-line shortcircuit

> 23 mA

Min. adjustment delta

2 % of the adjusted sensor values

Connection line

2-wire (standard line)

Resistance per conductor

max. 35

Resolution

1

µ

A

Linearity error

0,025 % at 4 … 20 mA

Temperature error

0,04 %/10 K at 4 … 20 mA

Measuring data input VEGAMET 514 VD

Number

1 input

Data transmission

digital (VBUS)

Sensor

hydrostatic pressure transmitters,
ultrasonic or radar sensor

Voltage

appr. 25 V DC

Power limitation

at appr. 7 W, shortcircuit proof

Connection line

2-wire (screened)

Line length

max. 1000 m

Resistance per conductor

max. 200

for hydrostatic pressure transmitters

max. 20

for ultrasonic or radar sensors

Correction signal input

Number

1 input

Function

switching signal to trigger and offset correction

Voltage

5 V (from instrument)

Current

5 mA

External line resistor

150

Product description

>>