8 set-up, additional functions, 1 password, 2 linearization curve 1 … 3 – VEGA VEGAMET 514… D User Manual
Page 43
VEGAMET 514… D
43
4.8 Set-up, additional functions
4.8.1
Password
Additional functions
–– Password
off
each menu point can be enquired and modified
on
the password can be enquire menu point with [+]
and [–].
With the adjustment of password the whole menu is
released again.
Password for
VEGAMET 514 D … and 514 VD = -0514-
4.8.2
Linearization curve 1 … 3
A linearization curve is generated by a certain
number of index markers and their value pairs. A
value pair consists of a value for level percent (X %)
and a value for volume percent ( Lin %). Up to max.
32 index markers can be added.
A linearization curve can be terminated after any
individual number of index markers. The signal
conditioning instrument terminates automatically the
linearization curve with the values X = 100 % and
Y = 100 %.
The input of a linearization curve is made in the
menu point "Add index marker".
4.7.6
Parameter adjustment MST1 and MST2, special functions
Parameter adjustment MST1 and MST2, special functions
–– Reset meas. point (e.g. level or flow)
Reset of all parameter values of the meas. point
–– Reset OK?
MST1 or MST2 with this reset to factory
–– Reset now! OK?
setting.
–– Failure mode
Standard
no fault signal
<–10%
Fault signal with decreasing and/or exceeding
<110%
of the adjusted measuring range
>110%
<-10a.>110%
<-110a.>110%
–– Manual corrections
–– Offset correction
Only visible with hydrostat. pressure transmitters.
Carry out correction only with unpressurized sensor.
–– Offset correction OK?
–– Correction now! OK?
Set-up, parameter adjustment
>>