beautypg.com

4 parameter adjustment mst1 and mst2, outputs – VEGA VEGAMET 514… D User Manual

Page 35

background image

VEGAMET 514… D

35

Set-up, parameter adjustment

4.7.4

Parameter adjustment MST1 and MST2, outputs

Parameter adjustment MST1 and MST2, outputs

–– Current outputs

–– Current output 1

acc. to basic configuration coordinated to MST1, i.e. 0 … 20 mA
relating to level

–– relating to

Percent

etc. choice acc. to list

–– Unit

%

etc. choice adapted to above determination

–– Current output

4/20 mA

0/20 mA
20/4 mA

20/0 mA

-free-

activated the menu points "Current at 0% and 100%"

–– Current at 0 %

4 mA

adjustable range 0.0 … 20.0 mA

–– Current at 100 %

20 mA

adjustable range 0.0 … 20.0 mA

reaction of the current output in case of failure

–– at failure

0 mA

0 mA

22 mA

22 mA

--

actual current value is kept

0 %

current value relating to 0 %

100 %

current value relating to 100 %

–– Current output 2

acc. to basic configuration coordinated to MST2, i.e. 0 … 20 mA
relating to flow, otherwise like current output 1. The output can be also

configured for pulses, see menu range of current output 3

–– Current output 3

acc. to basic configuration coordianted as pulse output MST2

–– Kind

Pulse output

Sampling

output

>>

Parameter,
flow

Parameter,
flow

t

20 mA

0 mA

t

20 mA

0 mA