4 parameter adjustment mst1 and mst2, outputs – VEGA VEGAMET 514… D User Manual
Page 35
VEGAMET 514… D
35
Set-up, parameter adjustment
4.7.4
Parameter adjustment MST1 and MST2, outputs
Parameter adjustment MST1 and MST2, outputs
–– Current outputs
–– Current output 1
acc. to basic configuration coordinated to MST1, i.e. 0 … 20 mA
relating to level
–– relating to
Percent
etc. choice acc. to list
–– Unit
%
etc. choice adapted to above determination
–– Current output
4/20 mA
0/20 mA
20/4 mA
20/0 mA
-free-
activated the menu points "Current at 0% and 100%"
–– Current at 0 %
4 mA
adjustable range 0.0 … 20.0 mA
–– Current at 100 %
20 mA
adjustable range 0.0 … 20.0 mA
reaction of the current output in case of failure
–– at failure
0 mA
0 mA
22 mA
22 mA
--
actual current value is kept
0 %
current value relating to 0 %
100 %
current value relating to 100 %
–– Current output 2
acc. to basic configuration coordinated to MST2, i.e. 0 … 20 mA
relating to flow, otherwise like current output 1. The output can be also
configured for pulses, see menu range of current output 3
–– Current output 3
acc. to basic configuration coordianted as pulse output MST2
–– Kind
Pulse output
Sampling
output
>>
Parameter,
flow
Parameter,
flow
t
20 mA
0 mA
t
20 mA
0 mA