VEGA VEGAMET 514… D User Manual
Page 27

VEGAMET 514… D
27
Set-up, parameter adjustment
Adjustment
- Application
Flow measurement
- Sensor
ultrasonic sensors
radar sensors
Parameter adjustment MST1, adjustment
–– with measured product
With this adjustment procedure %-values have to be
adjusted each for min. and max. which correspond
to the actual measured distances between sensor
and level/flow.
–– Min. adjustment at
0.0 %
Range 0 … 80 %
–– Max. adjustment at
100.0 %
Range 20 … 100 %
a
∆
of 20 % must be observed between min. and
max.
–– without measured product
For this adjustment procedure two future distances
(sensor … level/flow) must be adjusted which
correspond to 0 % and 100 %.
–– Adjustment in
m (d)
etc. if necessary modify unit, the unit is displayed
acc. to the menu point "Adjustment in"
–– 0 % at
0.80 m(d)
0.80 and 1.40
–– 100 % at
1.40 m(d)
corresponds e.g. to adjustment distances in m
Parameter adjustment MST2, adjustment as described above
If you want to detect the level and the flow as parameter, it is recommended to carry out the adjustment for
MST1 and MST2 at the same time, i.e. immediately one of the other.
e.g. rectangular weir
h
max.
= 0,60 m
100 % ^ 0,80 m (d)
0 % ^ 1,40 m (d)