E029
Measured valuated. The measured value is generated by simulation and does not reflect the
real condition.
E031
Same DISBUS-address. At least another instrument with the same DISBUS-address is
connected to this instrument. Please check the DISBUS-address.
E032
Instrument address 0. Instrument address 0 is adjusted on VEGAMET. With this address
VEGAMET does not participate in the DISBUS-communication, even the DISBUS is wired. If
necessary modify the instrument address.
E034
Instrument error. A considerable error was detected on the instrument (possibly defect
EEPROM). Please disconnect voltage and then connect again (cold start). If the error does
not extinguish, please contact your VEGA-agency.
E035
Instrument error. A considerable error was detected on the instrument (possibly check sum
error in EEPROM). Please disconnect voltage and then connect again (cold start). If the
error does not extinguish, please contact your VEGA-agency.
E050
Remote VEGAMET not found. The VEGAMET from which a measured value is expected,
cannot be found.
Reasons:
- the remote VEGAMET is not connected
- no VEGAMET with this instrument address connected
- line break (DISBUS)
- shortcircuit (DISBUS)
- the remote VEGAMET is defect
- interfered communication (DISBUS)
probably
- interference in the DISBUS-transmitter/receiver part of VEGAMET
Please check the instrument address on both VEGAMET, the connection line, the remote
VEGAMET and if necessary this VEGAMET.
E051
Failure during the transmission of measured values via DISBUS. It is not possible to receive
a valid measured value via DISBUS from the remote VEGAMET; the communication to the
remote VEGAMET however is okay.
Reasons:
- failure on the remote VEGAMET
- the input of the remote VEGAMET which should be transmitted, is not yet configured
Please check the remote VEGAMET and if necessary its input configuration.
E052
Input number not yet coordinated.
E053
Span of the sensor characteristic values too small.
E054
Sensor characteristic values exchanged.
E055
The hysteresis on the correction signal input is too small.
E060
Span of the current output values too small. The values for the current output are too close
together or are identical. Please check the adjustment of the current output.
E061
Span of the voltage output values too small. The values for the voltage output are too close
together or are identical. Please check the adjustment of the voltage output.
E062
Pulse parameters too small. The pulse parameters in relation to the max. flow are too small,
i.e. with this adjustment the time between two pulses would be less than one second. Please
check the relation of pulse parameters to max. flow.