Mounting
2.2 Instrument address
Adjust the instrument address on the appropriate switch on the circuit board. Address range 1 ...15. Observe
that no address is used twice. Factory setting = instrument address 0.
corresp.
10
11
12
13
14
15
514 D Ex
Switch on bottom, visible through
an appropriate opening
514 VD
Switch
Ex-version
Note!
Signal conditioning instruments must be generally
mounted outside hazardous areas or special Ex-
protective measures must be taken.
Ex-separating chamber
To ensure sufficient "air and creeping distances", an
Ex-separating chamber must be mounted to the
connections of VEGAMET. Lead the wires through the
Ex-separating chamber and connect them. Fasten
the Ex-separating chamber with the lower screw.
Observe the operating instrumention of carrier
BGT 596 Ex.M.
Protection for Ex-applications
In Ex-applications a protection of IP 20 must be kept.
Cover the spaces or not used modules from the front
by appropriate blind covers.
Mounting in carriers
If you mount your VEGAMET with Ex-approval in a
carrier, you have to use a VEGA-Ex-module. Keep a
distance of at least 10 mm (2 TE) to modules of other
manufacturers. If you want to mount the VEGAMET in
the extreme left position in the carrier, you have to
mount a blind cover of at least 20 mm (4 TE) in front
of the module of the instrument.
Blind cover
on
VEGAMET
515 N
ESC
OK
-
+
100
%
CONNECT
Under the menu point "Instrument address" ´the
adjustment carried out on the switch can be
indicated.