Set-up, parameter adjustment

Parameter adjustment MST1, outputs

–– Relay outputs

–– Relay output 1

acc. to basic configuration coordinated to MST1, i.e. level

–– relating to

Percent

etc. choice acc. to list

–– Unit

%

etc. choice adapted to above determination

–– Kind

Overfill protection
Prot. against dry running of pumps

Switching window

Off

Switching window

Off see additionally page 38 … 40

Tendency rising

Tendency falling
Monitoring

–– Low

0.0 %

In these menu points the switch points can be

–– High

100.0 %

determined for above relay modes (except

"Tendency rising" and "Tendency falling").

Range and unit acc. to selection in menu point
"relating to" and "Unit", see above

Reaction of the relay output in case of failure

–– at failure

off

- Relay de-energizes

--

- Actual switching condition is kept

–– additional functions

–– Switching delay

–– t on

0 s

Switch on delay

–– t off

0 s

Switch off delay

–– Relay output 2

see page 41

>>