34
VEGAMET 514… D
Set-up, parameter adjustment
Parameter adjustment MST2, processing (flow)
With the scaling of MST2 the conditions for the signal
conditioning instrument is provided to calculate the
flow volume/time. The respective values for min. and
max. flow are generally stated by the flume
manufacturers or can be calculated as proximity
values (see page 29 … 32).
In case of calculation the value of min. flow is
unimportant.
Example relating to a rectangular flume (see page
31):
- Max. flow 1385 m
3
/h
- Min. flow 4,4 m
3
/h
Parameter adjustment MST2, processing (flow)
–– Scaling
–– 0 % corresponds to
0
Range 0 … (4) … 9999 (Min. flow)
–– 100 % corresponds to
1000
Range 0 … (1385) … 9999 (Max. flow)
This value (1385) is automatically transferred to the
menu point "Pulse parameter volume", see page 36
and 41.
–– Decimal point
888.8
.8888
–– relating to
flow
–– Unit
L/s
etc. choice adapted to flow measurement
–– Linearization curve
linear
Given curves for flumes and
Root funct.
series
Venturi
Palmer-Bowlus
Quadrant
V-Notch
Trapezoidal weir
Rectangular overflow
Lin.curve 1
Enquiry of three curves to be edited
Lin.curve 2
Editing see page 43
Lin.curve 3
After a scaling or linearization the requested output must be coordinated to the scaled or linearized
value in the menu range "Parameter adjustment outputs", see menu points "relating to" and "Unit".
–– Integration time
0 s
Range 0 … 600 sec.
100 %
^ 1385 m
3
/h
4,4 m
3
/h