Installation guide, Setup, Entering setup mode – Veris Industries H8936 Install User Manual
Page 7: Setup mode sub-menus, Status led and relay operation, Monitoring mode, Alarm mode

Z202662-0G
PAGE 7
©2012 Veris Industries USA 800.354.8556 or 1.503.598.4564 / [email protected]
09126
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
H8932/H8936
INSTALLATION GUIDE
SETUP
Use the Setup mode to initialize and configure the display to the application
requirements. Use Setup Sub-menus to group parameters for setup.
Entering Setup Mode
UP
DOWN
To Enter
(SELECT, DOWN, DOWN, SELECT, UP, UP)
UP
SELECT
DOWN
METER
Show next
submenu
Show previous
submenu
Return to
monitoring
Go to submenu
or start action
Setup Mode
Press Simultaneously
Press
Enter Password
* * * * * * *
Setup Mode Sub-Menus
After entering the password (Select, Down, Down, Select, Up, Up), the device enters
the Setup Mode Sub-Menus. Scroll through these menus using the Up or Down
buttons, and enter a menu by pressing Select.
1. VIEW SYSTEM INFO: Lists the model number and firmware version of the device.
2. FIND METERS: Initiates a search and identifies meters on the network. Exit the
search by pressing any key (do not exit until all active addresses have been
counted). Unsupported devices are designated as “unknown device,” and
parameters are not displayed.
3. REVIEW METERS: Review all meters on the network.
4. SETUP COMMUNICATIONS: Scroll through this list of available parameters using
the Select button; change a parameter value using the Up and Down buttons.
Increment
parameter
Decrement
parameter
Return to
setup menu
Go to next
parameter
DOWN
UP
SELECT
METER
Communications Parameters:
Address Routing (On, Off)
Modbus Address (1-247)
Upstream Type (RS-485, RS-232)
Upstream Duplex (2-wire, 4-wire) (not available for RS-232)
Upstream Baudrate (2400, 4800, 9600, 19200)
Upstream Parity (NONE, ODD, EVEN)
Downstream Duplex (2-wire, 4-wire)
Downstream Baudrate (2400, 4800, 9600, 19200)
Downstream Parity (NONE, ODD, EVEN)
5. SETUP OPERATION: Scroll through this list of available parameters using the Select
button; select a parameter value using the Up and Down buttons.
Increment
parameter
Decrement
parameter
Return to
setup menu
Go to next
parameter
DOWN
UP
SELECT
METER
Operation Parameters:
Backlight Brightness (0-9; 0 = off)
Auxiliary Input (open, closed)
Rotate Parameters (Yes, No)
Status LED and Relay Operation
The status LED displays the condition of the alarm registers on a color cue basis.
Green: normal operation (no networked devices are in warning or alarm
mode)
Yellow: warning (one or more networked devices are in warning mode)
Red: alarm (one or more networked devices are in alarm mode or the
auxiliary input is active).
Monitoring Mode
Monitoring mode is the default mode for the H8932/H8936. In monitoring mode, the
data values are updated at 4-second intervals. The H8932/H8936 can be set either
to cycle automatically through all parameters on all devices or to display a selected
parameter continuously.
Go to the next
parameter set.
Go to the previous
parameter set.
Go to the
next meter
Hold a reading on
the LCD (display will
flash).
For use in automatic
cycle mode (See Setup
Operations).
The current reading does
not update, allowing time
to manually record the
reading. Press any
other button to release
the held reading.
DOWN
UP
SELECT
METER
Alarm Mode
Alarm Mode provides a means of viewing and resetting warnings and alarms on the
downstream network. To enter Alarm mode, press the Select and Meter buttons
simultaneously.
Go to the
next alarm.
Reset the currently
displayed alarm.
Exit the alarm
display.
To Enter
Alarm Menu
Press Simultaneously
Press
UP
SELECT
SELECT
METER
METER