Veris Industries H8936 Install User Manual
Danger, Notice, Warning
Z202662-0G
PAGE 1
©2012 Veris Industries USA 800.354.8556 or 1.503.598.4564 / [email protected]
09126
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
NETWORK INTEGRATION
INSTALLATION GUIDE
Specifications
AC Power Source
Dedicated 120/240 VAC, line-to-neutral; fused
Fuse Ratings
200mA at 250V 5x20 mm fast blow
AC Power Voltage Tolerance
90-132VAC for 120V
AC Power Frequency
50/60 Hz
AC Power Termination
2-position Euro style pluggable connector
(max. wire size 12 gauge)
Terminal Block Torque
4.9 in-lb (0.56 N-m)
Alternate DC Power Source
12VDC, 300mA unfused
Environmental:
Operating Temperature Range
0° to 50°C (32° to 122°F)
Operating Humidity Range
<95% RH, non-condensing
Storage Temperature Range
-20° to 70°C (68° to 158°F)
Network Communications:
Interface
Downstream: RS-485; Upstream: RS-485, RS-232
Protocol
Modbus RTU
Baud Rate
UI-selectable 2400, 4800, 9600, 19200
Parity
UI-selectable NONE, ODD, EVEN
Communication Format
8-data-bits, 1-start-bit, 1-stop-bit
RS-485
¼ load transceivers; duplex is UI-selectable 2-wire or 4-wire;
5-position Euro-style pluggable connector
RS-232 (Upstream only)
DCE, no handshaking; DB-9 connection;
pin
2: transmitted data from display;
pin
3: received data to display; pin 5: ground
Terminal Block Torque
4.4 in-lb (0.5 N-m)
UI Switch Inputs:
Number/Function
4 (Meter, Up, Down, Select)
Auxiliary Input (Remote Alarm):
Type
Contact closure or pull-to-ground
Isolation
Optical to 2500VAC
Sense
UI-selectable N.O. or N.C.
Terminal Block Torque
3.5 to 4.4 in-lb (0.4 to 0.5 N-m)
LCD:
Size
1” x 4” visible area, 2 lines x 16 characters per line
Backlight
Green, UI-adjustable brightness in 10 steps
Status (Tri-Color LED)
Green = normal operation; Yellow = warning; Red = alarm
Network Display
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualified person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved.
NEC2009 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
DANGER
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
PRODUCT IDENTIFICATION
MODEL
DESCRIPTION
H8932
without enclosure
H8936
with enclosure
H8932/H8936
SUPPORTED METERS
MODEL
DESCRIPTION
H8035/H8036
Enercept Power Meter
H8163 with H8163-CB
Energy Meter
H663/H704
Branch Circuit Meter
H8238
Multi-Circuit Monitor
E5xCx
Power and Energy Meter, Modbus Protocol versions
E30/E31
Panelboard Monitoring System
WARNING
LOSS OF CONTROL
∙ Assure that the system will reach a safe state during and after a control path failure.
∙ Separate or redundant control paths must be provided for critical control functions.
∙ Test the effect of transmission delays or failures of communication links.
1
∙ Each implementation of equipment using communication links must be individually
and thoroughly tested for proper operation before placing it in service.
Failure to follow these instructions may cause injury, death or equipment damage.
1
For additional information about anticipated transmission delays or failures of the link, refer to
NEMA ICS 1.1 (latest edition). Safety Guidelins for the Application, Installation, and Maintenance
of Solid-State Control or its equivalent in your specific country, language, and/or location.
Control system design must consider the potential failure modes of control paths and, for
certain critical control functions, provide a means to acheive a safe state during and after a
path failure. Examples of critical control functions are emergency stop and over-travel stop.