Installation guide, Network configuration, Wiring the network(s) – Veris Industries H8936 Install User Manual
Page 5: Network map: option 1, Network map: option 2, Next previous hold scroll

Z202662-0G
PAGE 5
©2012 Veris Industries USA 800.354.8556 or 1.503.598.4564 / [email protected]
09126
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
H8932/H8936
INSTALLATION GUIDE
NOTE: The manufacturer does not recommend connecting multiple network displays in series on
the downstream network.
NOTE: Other Modbus devices must respond to the “Report Slave ID” command (11h) to allow pass-
through communication from the upstream network.
NETWORK CONFIGURATION
Wiring the Network(s)
The H8932/H8936 resides on a Modbus network as a pass-through device. Unlike
most Modbus RTU devices, it is not wired in a daisy chain configuration. This allows
the user to make separate upstream and downstream networks, allowing for flexible
data retrieval, as the upstream options include RS-232 or RS-485.
Network Map: Option 1
Control Panel
or PC
Next Network Display
On to additional Network Displays
Network Display
H663/H704
Branch Circuit Monitor
H8163 with H8163-CB
Energy Meter with
Communication Board
H8035/H8036
Enercept Power Meter
H8238
Multi-Circuit Monitor
E30/E31
Panelboard Monitor
E5xCx
Power and Energy Meter
End-of-Line
Termination Resistor
100 Ohms
Upstream RS-485
or
RS-232
Downstream RS-485
Up to 63 (physical) or 246 (logical) devices
UP
DOWN
SELECT
METER
ALARM
OPERATING MODE
NETWORK DISPLAY
VERIS INDUSTRIES
SETUP
NEXT
PREVIOUS
HOLD
SCROLL
UP
DOWN
SELECT
METER
ALARM
OPERATING MODE
NETWORK DISPLAY
VERIS INDUSTRIES
SETUP
NEXT
PREVIOUS
HOLD
SCROLL
Network Display
Downstream RS-485
H663/H704
Branch Circuit Monitor
H8163 with H8163-CB
Energy Meter with
Communication Board
H8035/H8036
Enercept Power Meter
H8238
Multi-Circuit Monitor
E30/E31
Panelboard Monitor
E5xCx
Power and Energy Meter
End-of-Line
Termination Resistor
100 Ohms
Up to 63 (physical) or 246 (logical) devices
Network Map: Option 2