Installation Guide

Power Monitoring

H81xx

TM

The following messages remain on the lower display for the duration of an alarm condition:

Message

Explanation

Phase loss

The voltage on one phase is less than 75% of the voltage on any other

phase. The displayed message indicates the problem phase.

Amps Over

The measured current is greater than 110% of the transformer range. The

display message indicates the problem phase.

Volts Over

Volts A-C, B-C, or A-C is greater than 660VAC.

*

The displayed message

indicates the problem phase.

*

The H8163 and H8167 are rated to 300 VAC L-N, and the H8150 is rated to 132 VAC L-N. Operation above these levels damages the device.

Alarms

The H81xx continually reports kWh or MWh, depending on the total accumulated energy. A secondary display cycles through other
parameters. The meter has two modes of display operation, depending on the setting of the Display Data jumper (J8) on the main
circuit board. In Full Display mode, the meter cycles through all parameters. In Plain Display mode, the meter cycles through only
the first five parameters as listed below:

kW
Max. kW
PF
Volts
Amps
kVAR
kW, phase A *
kW, phase B *
kW, phase C **
PF, phase A *
PF, phase B *
PF, phase C **
Volts, A-B **
Volts, B-C **
Volts, A-C **
Volts, A-N *
Volts, B-N *
Volts, C-N **
Amps, A *
Amps, B *
Amps, C **

If the H81xx has a communication board installed, every 10th rotation of parameters displays an additional set of data values:

Pulse Rate ***
Address
Baud Rate
Parity
2/4 Wire

* For meters with 2 or 3 current transformers.
** For meters with 3 current transformers.
*** H8163 and H8167 only.

Data Outputs