beautypg.com

Troubleshooting, Installation guide power monitoring h81xx – Veris Industries H81xx SERIES Install User Manual

Page 10

background image

Z205338-0F

Page 10 of 10

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 09132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

H81xx

TM

Problem

Solution

No display

· Check external fuses.
· Verify that the display cable has not been disconnected during installation.
· Verify voltage leads are properly connected.

Reported power too low

· Verify CTs and terminals are color-matched.
· Check for phase loss.
· Check external fuses.

Reported power inaccurate

Verify meter and CTs have matching serial numbers (serial number matching does not apply if using

100 A CTs).

Accuracy not as specified

· Verify CTs and terminals are color-matched.
· Verify that no stray conductive materials (wire clippings, etc.) have shorted between the terminals.

No Pulse output (H8163 and H8167)

· Verify power is supplied in the range of 5-24 VAC/DC, with a max. load of 100 mA.
· The pulse output internal is 200 msec; verify the controller accepts this signal as input.

Pulse output wrong, display OK (H8163

and H8167)

Set the pulse rate switch and the controller to match kWh/pulse.

No Phase Loss output (H8163 and

H8167)

Verify power is supplied in the range of 5-24 VAC/DC, with a max. load of 100 mA.

“bAd” appears in the display (H8163

and H8167)

Verify that the Pulse Rate slide switch is set to a valid value. 0.1 is not valid for 1600 A systems; 0.1

and 0.25 are not valid for 2400 A systems.

Accuracy not as specified

Verify current transformers and terminals are color-matched.

Troubleshooting