COMMISSIONING

1. Reconnect power to the panel.

2. Configure installation mode using Modbus Register 6.

3. Configure CT scaling.

4. Configure alarms.

5. Configure demand.

Download the free E3x configuration tool from www.veris.com to commission the
device for operation.

RECOMMENDED ACCESSORIES

Part ID

Description

CBL008

Flat ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)

CBL016

Flat ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)

CBL017

Flat ribbon cable, 50 x 28 AWG, 5 ft. (1.5 m)

CBL018

Flat ribbon cable, 50 x 28 AWG, 6 ft. (1.8 m)

CBL019

Flat ribbon cable, 50 x 28 AWG, 8 ft. (2.4 m)

CBL020

Flat ribbon cable, 50 x 28 AWG, 10 ft. (3.0 m)

CBL021

Flat ribbon cable, 50 x 28 AWG, 20 ft. (6.1 m)

CBL022

Round ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)

CBL023

Round ribbon cable, 50 x 28 AWG, 10 ft. (3 m)

CBL024

Round ribbon cable, 50 x 28 AWG, 20 ft. (6 m)

CBL025

Flat ribbon cable, 50 x 28 AWG, 2 m

CBL026

Flat ribbon cable, 50 x 28 AWG, 4 m

CBL027

Flat ribbon cable, 50 x 28 AWG, 6 m

CBL031

Round ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)

CBL032

Round ribbon cable, 50 x 28 AWG, 2.5 ft. (0.76 m)

AE001

E3x MCB cover

AE006

E30 CT repair kit

H8932/H8932

Network Display

SAFETY

If Veris E30 products are used in installations with circuits higher than the product
ratings, the circuits must be kept segregated per UL508A Sec. 17.5.

Note: 277/480 VAC Wye connected (center grounded) power systems operate
within the 300 VAC line to neutral safety rating of the E3x series, and the
operational voltage limit (single-phase connection) as the line to neutral
voltage is 277 VAC in such power systems. Corner-grounded delta 480 VAC
systems would not qualify, as the actual line to earth voltage is 480 VAC on
each leg, exceeding the E3x ratings.

Note: E3x internal circuitry (cables and CTs) are not circuits as defined by
UL508A, as they do not extend beyond the E3x itself without further safety/
fire isolation.

UL listed under standard 508 as an “open type device.”

Maximum ambient air temperature for use is 60°C.

The E30 Series must be installed in an appropriate electrical and fire enclosure per
local regulations.

Installation category: CAT III

For use in a Pollution Degree 2 or better environment only.

A Pollution Degree 2 environment must control conductive pollution and the
possibility of condensation or high humidity. Consideration must be given to the
enclosure, the correct use of ventilation, thermal properties of the equipment and the
relationship with the environment.

If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the device may be impaired.

IEC/EN 61010-1

This symbol indicates an electrical shock hazard exists.

Documentation must be consulted where this symbol is used on the
product.