M&C TechGroup FA1-H-.. Data sheet User Manual

Optical flow monitoring series fa, Special features, Application

background image

M&C TechGroup Germany GmbH • Rehhecke 79 • 40885 Ratingen • Germany

[email protected] • www.mc-techgroup.com • Fon +49 2102 935-0 • Fax +49 2102 935-111

9.6

Embracing Challenge

ƒ

ƒ

Easy mounting of the sensor head at the
flow meter without dismounting the
measuring glass

ƒ

ƒ

Also applicable for very low flow quanti-
ties

ƒ

ƒ

Also suitable for non-metallic or very
small floating balls

ƒ

ƒ

Easy adjustment of any MIN alarm set-
point

Special Features

Optical flow monitoring series FA®

Version FA1-H-.. for temperatures up to 180 °C
with 2 light guides for monostable functioning

FA2-H, 2 x F01, K-FA-H, FA-1.1

Application

The optical flow monitoring unit with light

guides is used in gas analysis on heated

flowmeters with temperatures > 60 °C. The

measuring cones must be transparent.
Thanks to optical scanning, very low flow

quantities can be recorded even in case of

flowmeters with non-metallic or very small (1

mm) floats.

Description

The M&C flow monitoring unit FA1-H-.. con-

sists of 4 sub-assembly modules:

1. the patented sensor head FA2-H,
2. the 2 light guides FO.. for monostable

function

3. the K-FA-H pre-amplifier
4. the electronic controller FA-1.1 or

FA-1.4**

– ** see data sheet FA-.., K-FA 9.5 –

The sensor head FA2-H is assembled on the

FM1-H flowmeter by means of a pressure

screw with its stationary open prism to the

measuring glass. Assembly is simple and does

not require any disassembly of the flow-

measuring glass.
The FO1 light guide is supplied with a stand-

ard length of 600 mm. Light guide FO3 (900

mm long) and FO2 (1200 mm long) can be

supplied for greater length requirements.
The angled light-guide ends are fixed into the

FA2-H sensor head with one pressure screw

each. Two light-guides are needed for the

monostable function.
By use of the pre-amplifier K-FA-H a distance

of 200 meters between the flow meter and

the electronic controller FA-1.. (see 9.5) is pos-

sible without problems.

The LED emitters’ light beam passes through

the FO .. light guides and falls upon the

photo-transistor through the FM1-H

flowmeter measuring glass. As soon as the

float breaks the light beam, the photo-tran-

sistor is blacked out. The FA-1.. electronic con-

troller analyses this changed status accord-

ingly.
By the monostable version a MIN alarm func-

tion in the lowest sensor setting position is

guaranteed.