Table 3-2. Port C Signal Assignments

Programmable

Mode

Group A

Group B

PC7

PC6

PC5

PC4

PC3

PC2

PC1

PC0

Mode 0

I/O

I/O

I/O

I/O

I/O

I/O

I/O

I/O

Mode 1 Input

I/O

I/O

IBFA

STBA*

INTRA

STBB*

IBFBB

INTRB

Mode 1 Output

OBFA*

ACKA*

I/O

I/O

INTRA

ACKB*

OBFB*

INTRB

Mode 2

OBFA*

ACKA*

IBFA

STBA*

INTRA

I/O

I/O

I/O

*Indicates that the signal is active low.

Timing Specifications

The handshaking lines STB* and IBF are used to synchronize input transfers. The handshaking
lines OBF* and ACK* are used to synchronize output transfers.

The following signals are used in the timing diagrams shown later in this chapter:

Name

Type

Description

STB*

Input

Strobe input–A low signal on this handshaking line loads data into
the input latch.

IBF

Output

Input buffer full–A high signal on this handshaking line indicates
that data has been loaded into the input latch. This is primarily an
input acknowledge signal.

ACK*

Input

Acknowledge input–A low signal on this handshaking line
indicates that the data written from the specified port has been
accepted. This signal is primarily a response from the external
device that it has received the data from the Lab-PC+.