Page 55

background image

Connecting the server to power

55

2

Plug the other end into a wall receptacle or power bar.

—End—

To connect the 1002rp DC server to power

Step

Action

DANGER

Only qualified personnel can alter electrical connections.

Ensure the power distribution unit (PDU) is turned off
until you are instructed to turn it on.

1

Connect the DC power cable to the server.

2

Connect the other end of the DC power cable to the PDU. Use the
supplied clips and screws to secure the plugs.

The following photograph shows the keyed plug of the DC power
cable. This plug connects to the PDU:

Note: If you are not using a Nortel-supplied PDU, have a
qualified electrician connect the cable appropriately to your DC
power plant. The 1002rp uses a negative 48 V power supply,
therefore the red cable is negative (-48 V) and the black cable is
the ground (GND).

3

Turn on the PDU.

Nortel CallPilot

1002rp Server Hardware Installation

NN44200-300

01.01

Standard

5.0

23 February 2007