DC wire gauge tables

Introduction

The tables in this section specify the DC power feed wire requirements.

Cabinet and module DC feed recommended wire gauge specifications

Length

#10 AWG

#8 AWG

#6 AWG

Junction
box #4
AWG

Junction
box #4
AWG

0-30 m (100 ft)

yes

yes

yes

yes

yes

0-45 m (150 ft)

no

yes

yes

yes

yes

0-75 m (250 ft)

no

no

yes

yes

yes

0-135 m (450 ft)

no

no

no

yes

yes

Notes:

1.

The cabinet and module ground wire specification is #10 AWG insulated green safety ground wire.

2.

The cabinet conduit can be 19.1 mm (0.75-in.) or 31.8 mm (1.25-in.), and must be insulated