Polycom DOC2238A User Manual
Page 29
MGC+ Hardware and Installation Manual
2-9
1.
Check that all the parts are in the kit.
The kit should contain the following items:
2.
Make sure that the MCU power is turned OFF and it is disconnected
from the AC power.
Remove the side covers as described on page 2-4.
3.
If the MCU is a standalone unit, you must first remove the side covers,
and add the mounting brackets to a 23” rack (see pages 2-4 to 2-6).
4.
Attach the two mounting bars to the MCU as follows:
a.
Fit the spring washer (Item #3) onto the screw (#2).
Because of heat considerations, the MCU must be installed with the Control Unit
Module placed on the left bottom.
Table 2-1: 19” Rack Mounting Kit
Item #
Polycom P/N
Description
Quantity
1
MEC2063A
23" TO 19" Mounting Bar
MGC+100 at 90 Degrees
2
2
SCR2005A
Screw 10-32 x 1/2” Allen S/H
ST/ST
8
3
WAS2003A
Washer M5 Spring Latch Loc.
ST\ST
8
4
WAS2004A
Washer M5 Flat ST/ST
8
Item #3