beautypg.com

Internal leds, connectors, and jumpers – Lenovo THINKSERVER 3821 User Manual

Page 148

background image

Table 8. Power-supply LEDs

Power-supply LEDs

Description

Action

Notes

ac

dc

Error

Off

Off

Off

No ac power to
the server or a
problem with the
ac power source

1. Check the ac power to the server.

2. Make sure that the power cord is

connected to a functioning power
source.

3. Turn the server off and then turn the

server back on.

4. If the problem remains, replace the

power supply.

This is a normal
condition when no
ac power is present.

Off

Off

On

No ac power to
the server or a
problem with the
ac power source
and the power
supply had
detected an
internal problem

1. Replace the power supply.

2. Make sure that the power cord is

connected to a functioning power
source.

This happens only
when a second
power supply is
providing power to
the server.

Off

On

Off

Faulty power
supply

Replace the power supply.

Off

On

On

Faulty power
supply

Replace the power supply.

On

Off

Off

Power supply not
fully seated,
faulty system
board, or faulty
power supply

1. Reseat the power supply.

2. If the system board error LED is off,

replace the power supply.

3. (Trained service technician only) If the

system board error LED is on, replace
the system board.

Typically indicates
that a power supply
is not fully seated.

On

Off or

Flashing

On

Faulty power
supply

Replace the power supply.

On

On

Off

Normal operation

On

On

On

Power supply is
faulty but still
operational

Replace the power supply.

Internal LEDs, connectors, and jumpers

The illustrations in this section show the LEDs, connectors, and jumpers on the
internal boards. The illustrations might differ slightly from your hardware.

140

ThinkServer TD200x Types 3719, 3821, 3822, and 3823: Hardware Maintenance Manual

This manual is related to the following products: