OPERATION AND APPLICATION

UNILINK HOST ADAPTER

2–33

USER MANUAL

The total macro memory requirements can be calculated by summing the
memory for each individual macro. For example, suppose that you use one
macro to connect secondary #7, another macro to issue a Primitive 45 bytes long
expecting a response 30 bytes long, and another macro to disconnect secondary
#5. The total memory required for these three macros is:

Macro #1, Connect

= 22

= 22

22

Macro #2, Primitive

= 22 + 45 + 30

= 97(+1)

98

Macro #3, Disconnect = 22

= 22

22

"""

Total Memory Required

142 Bytes

Example 2–2 Macro Memory Requirements

Host
Computer

UNILINK

TIWAY I

UniLink Host Adapter

Job Directory
Job A
Job B
Job C

Figure 2–15 Host Computer Multiprocessing Application

Example