HOST COMMAND SET REFERENCE
UNILINK HOST ADAPTER
5–49
USER MANUAL
5.5.2
Report Adapter Configuration — 21
The REPORT ADAPTER CONFIGURATION command returns the values
specified in the CONFIGURE ADAPTER command. All parameters will be
returned, even the defaults.
Command:
21
Response:
21 dddddddd ff 01 vvvv 02 vvvv 03 vvvv 04 vvvv
Usage:
PERFORMANCE
Parameters:
dddd
The current values for Dipswitch 1 and Dipswitch 2 in the most
significant word and least significant word respectively. The
position values are right–justified in each word as shown in
Figure 5–8. A bit set to one indicates the corresponding switch is
up (off).
1
2
3
4
5
6
7
8
9
10
U
P
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
MSB
LSB
1
2
3
4
5
6
7
8
9
10
U
P
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
MSB
LSB
WORD #1
WORD #2
Dipswitch 1
Dipswitch 2
Figure 5–8 Dipswitch Values Bit Map
ff
A flag, that when set to one, indicates that the CONFIGURE
ADAPTER command has been processed. In multiprocessing
environments, the tasks can check the value of this flag to
determine if they can issue initiation, operation, and termination
commands.
vvvv
The parameters described in the CONFIGURE ADAPTER
command.