ERROR CODES AND DIAGNOSTICS

UNILINK HOST ADAPTER

6–3

USER MANUAL

008D

One of the ASCII characters between the beginning and ending
delimiters was not in the NITP character set. Valid NITP characters are
the ASCII values 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, and F. Retry the
message at least three times. If this same error returns all three times,
check for an error in your software driver.

100B

The HIU has not been initialized by the Network Manager causing the
adapter to be offline. Retransmit the command.

100C

There is not enough memory available to allocate an area to hold status
information for the requested secondary. You can deallocate resources
for a Source Id to gain enough memory for the secondary status
information. See the ALLOCATE SOURCE ID command, code 10.

100D

There is not enough memory available to allocate another Source Id.
You can deallocate resources for another Source Id to gain enough
memory to allocate this one.

100E

The bandwidth statistics for the requested HIU are not available
because the HIU has not been initialized by the Network Manager.

100F

You requested auto redundant mode without signifying that Channel B
was available or tried issuing the SWITCH CHANNEL command
without making Channel B. See the CONFIGURE NETWORK
MANAGER command, code 30, Option 01.

2002

The NM and HIU are not configured for an MHIU. You will need to issue
command code 30 to configure the NM and command code 11 to
configure the HIU.

2003

The NM is not configured. You will need to issue command code 30
before continuing.

2004

The HIU of the MHIU is not configured. You will need to issue command
code 11 before continuing.

2006

Your command string contained the same option code twice. Correct
and reissue the command.

2007

The HIU is already configured. You can only issue command code 11
once after each adapter reset.

2008

You tried to specify that one TIWAY I Port uses Local Line media and
that the other TIWAY I Port uses RS-232-C media. The media for both
ports or channels must be the same.