ERROR CODES AND DIAGNOSTICS
UNILINK HOST ADAPTER
6–2
USER MANUAL
000E
An uneven number of bytes was received from the secondary.
0010
Lost Data Carrier Detect (DCD) from the TIWAY I interface port(s).
0011
Lost Clear To Send (CTS) from the TIWAY I interface port(s).
0084
The command processor found an unrecognized command code in the
command string. This also indicates that the command code is not valid
for the currently configured operating mode. If you receive this error
after issuing one of the Extended HIU or NM commands, you can
assume that the adapter was reset and needs to be reconfigured.
0085
An invalid field was received with the command code. Check the
command syntax in Chapter 5.
0086
The length of the command frame received from the host was too long
for the specified command code.
0087
The length of the command frame received from the host was too short.
The minimum length for an NITP protocol frame is 11 bytes. The
minimum length for a BDLC protocol frame is 9 bytes.
0088
The secondary device addressed in the command string is not connected
to the TIWAY I network. Recheck the address in the command string
and the addresses of the secondary devices. Then, issue a CONNECT
SECONDARY command or enable a macro that was previously defined
to connect that secondary.
0089
The colon that begins an NITP message frame was missing. Correct the
frame and retransmit it.
008B
The character count field value did not match the number of characters
received. This could be caused by an error in the software driver. In
either case, your applications software should retry the message at
least three times. If this same error returns all three times, check for an
error in your software driver.
008C
The checksum calculated by the adapter did not match the
Error–Checking Code or the Block Checksum field value. Retry the
message at least three times. If this same error returns all three times,
check for an error in your software driver.