beautypg.com

Goodman Mfg MVC95 User Manual

Page 37

background image

37

S

TARTUP

P

ROCEDURE

& A

DJUSTMENT

H

EAT

A

NTICIPATOR

S

ETTING

The heat anticipator in the room thermostat must be correctly

adjusted to obtain the proper number of cycles per hour and to

prevent “overshooting” of the setting. Set the heat anticipator set-

ting to 0.7 amps. Follow the thermostat manufacturer’s instruc-

tions on how to adjust the heat anticipator setting.

D

RAIN

T

RAP

P

RIMING

The drain trap must be primed prior to furnace startup. To prime, fill

the drain trap with water. This ensures proper furnace drainage

upon startup and prohibits the possibility of flue gases escaping

through the drain system.

F

URNACE

O

PERATION

Purge gas lines of air prior to startup. Be sure not purge lines into

an enclosed burner compartment.

Check for leaks using an approved chloride-free soap and water

solution, an electronic combustible gas detector, or other approved

method. Verify that all required kits (propane gas, high altitude,

etc.) have been appropriately installed.

F

URNACE

S

TARTUP

1. Close the manual gas shutoff valve external to the furnace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.

NOTE: This furnace is equipped with an ignition device which

automatically lights the burner. Do not try to light the burner by

hand.

5. Move the furnace gas valve manual control to the OFF

position.

6. Wait five minutes then smell for gas. Be sure check near

the floor as some types of gas are heavier than air.

7. If you smell gas after five minutes, immediately follow the

Safety Instructions on page 5 of this manual. If you do not
smell gas after five minutes, move the furnace gas valve
manual control to the ON position.

8. Replace the burner compartment door.
9. Open the manual gas shutoff valve external to the furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room temperature.
12. After the burners are lit, set the thermostat to desired

temperature.

F

URNACE

S

HUTDOWN

1. Set the thermostat to the lowest setting.

The integrated control will close the gas valve and extinguish
flame. Following a 15 second delay, the induced draft blower
will be de-energized. After a 120, 150, 180 or 210-second
delay period (field selectable delay OFF [90, 120, 150, 180]
plus 30-second ramp down), the circulator blower de-
energizes.

2. Remove the burner compartment door and move the furnace

gas valve manual control to the OFF position.

3. Close the manual gas shutoff valve external to the furnace.
4. Replace the burner compartment door.

G

AS

S

UPPLY

P

RESSURE

M

EASUREMENT

CAUTION

T

O

 

PREVENT

 

UNRELIABLE

 

OPERATION

 

OR

 

EQUIPMENT

 

DAMAGE

THE

 

INLET

 

GAS

 

SUPPLY

 

PRESSURE

 

MUST

 

BE

 

AS

 

SPECIFIED

 

ON

 

THE

 

UNIT

 

RATING

 

PLATE

 

WITH

 

ALL

 

OTHER

 

HOUSEHOLD

 

GAS

 

FIRED

 

APPLIANCES

 

OPERATING

.

The line pressure supplied to the gas valve must be within the
range specified below. The supply pressure can be measured at
the gas valve inlet pressure boss or at a hose fitting installed in the
gas piping drip leg. The supply pressure must be measured with
the burners operating. To measure the gas supply pressure, use
the following procedure.

INLET

OUTLET

Gas Valve On/Off

Selector Switch

White-Rodgers Model 36G54 (Two-Stage)

Inlet

Pressure

Boss

Low Fire

Regulator

Adjust

Manometer

Manometer

Hose

High Fire Regulator

Adjust

Regulator

Vent

Outlet

Pressure Boss

Open to

Atmosphere

On/Off Switch

High Fire Coil

Terminal (HI)

Coaxial Coil

Terminal (M)

Common

Terminal(C)

White-Rodgers Model 36G54 Connected to Manometer

Gas Valve On/Off

Selector Switch

Regulator

Vent

High Fire

Regulator

Adjust

Low Fire

Regulator

Adjust

This manual is related to the following products: