Goodman Mfg MVC95 User Manual

Page 16

background image

16

V

ENT

/F

LUE

P

IPE

& C

OMBUSTION

A

IR

P

IPE

8. Upflow and Counterflow units.

For horizontal installations, externally secure the field-
supplied vent/flue pipe directly to the vent/flue coupling using
a PVC or ABS coupling or elbow.

A

LTERNATE

C

OMBUSTION

A

IR

I

NTAKE

L

OCATION

The alternate combustion air intake location consists of a large,
unobstructed hole (alternate vent connection is aligned with the
Induced Draft Blower). To use the alternate combustion air intake
location, refer to the following steps, and the “Alternate Combus-
tion Air Intake Location” figure.

1. Remove and save the four screws securing the combustion

air intake coupling to the basepan. Remove an additional
three screws securing the furnace’s internal combustion
air intake pipe to the blower deck.

2. Remove the combustion air intake pipe from the furnace

and cut the pipe at the basepan coupling. Save the basepan
coupling and gasket from the blower deck coupling for use
in the alternate location. Discard the remaining pipe.

3. Remove plastic plug from alternate combustion air intake

location. Relocate and install plug in standard air intake
location (basepan). Plug the remaining hole in the blower
deck with the plastic plug included in the drain kit bag.

4. With the gasket facing the cabinet side panel, and the

flange’s flat spot facing forward, secure the combustion air
intake coupling to the cabinet using the screws removed in
step 1 or with field-supplied 3/8” #8 self -drilling screws.

B

E

 

SURE

 

NOT

 

TO

 

DAMAGE

 

INTERNAL

 

WIRING

 

OR

 

OTHER

 

COMPONENTS

 

WHEN

 

REINSTALLING

 

COUPLING

 

AND

 

SCREWS

.

CAUTION

5. For non-direct vent installations installed horizontally, a

minimum of one 90° elbow should be installed on the

combustion air intake coupling to guard against inadvertent

blockage. No elbow is required on the alternate combustion

air intake of upright installations, however, a minimum

clearance of 2 inches is required to assure proper air supply.

6. For direct vent installations, secure field-supplied

combustion air intake pipe directly to the air intake coupling.
NOTE: A PVC coupling or elbow is required on counterflow
units.

5

ADDITIONAL PLUG

FROM DRAIN KIT

7

EXTERNALLY

MOUNT

RUBBER ELBOW

6

SECURE TO

ID BLOWER WITH

RUBBER COUPLING

AND HOSE

CLAMPS

3

REMOVE

PIPE

2

DETACH RUBBER

ELBOW FROM

ID BLOWER AND

VENT/FLUE

PIPE

2

DETATCH RUBBER

ELBOW FROM

ID BLOWER AND

VENT/FLUE

PIPE

3

REMOVE

PIPE

5

REMOVE

AND RELOCATE

5

REMOVE

AND RELOCATE

1

REMOVE

3 SCREWS

6

SECURE TO

ID BLOWER WITH

RUBBER COUPLING

AND HOSE

CLAMPS

6

SECURE TO

CABINET WITH

SCREWS

This manual is related to the following products: