Goodman Mfg MVC95 User Manual
Page 36
36
S
TARTUP
P
ROCEDURE
& A
DJUSTMENT
600
800
1000
1200
1400
1600
2000
0453__XA
376*
384
480
576
---
---
---
0704__XA
---
---
627*
627*
672
768
---
0905__XA
---
---
---
836*
836*
836*
960
1155__XA
---
---
---
940*
940*
940*
960
600
800
1000
1200
1400
1600
2000
0704__XA
0714__XA
---
---
320*
320*
336
384
---
0905__XA
0915__XA
---
---
---
427*
427*
427*
480
In
put
_
_
A
ir
fl
ow
UPFLOW
COOLING AIRFLOW REQUIREMENT (CFM)
COUNTERFLOW
COOLING AIRFLOW REQUIREMENT (CFM)
In
pu
t
Ai
rf
lo
w
*Minimum filter area dictated by heating airflow requirement.
Permanent Minimum Filter Area (sq. in)
[Based on a 600 ft/min filter face velocity]
600
800
1000
1200
1400
1600
2000
0453__XA
376*
384
480
576
---
---
---
0704__XA
---
---
564*
564*
672
768
0905__XA
---
---
---
752*
752*
768
960
1155__XA
---
---
---
940*
940*
940*
960
600
800
1000
1200
1400
1600
2000
0704__XA
0714__XA
---
---
641*
641*
672
768
---
0905__XA
0915__XA
---
---
---
854*
854*
854*
960
In
p
u
t_
_
A
ir
fl
o
w
UPFLOW
COOLING AIRFLOW REQUIREMENT (CFM)
COUNTERFLOW
COOLING AIRFLOW REQUIREMENT (CFM)
In
p
u
t
Ai
rf
lo
w
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter area (sq. in)
[Based on 300 ft/min filter face velocity]
U
PRIGHT
I
NSTALLATIONS
Depending on the installation and/or customer preference, differ-
ing filter arrangements can be applied. Filters can be installed in
the central return register or a side panel external filter rack kit
(upflows). As an alternative a media air filter or electronic air cleaner
can be used as the requested filter.
The following figure shows possible filter locations.
FIL
T
E
R
AIR FLOW
CENTRAL
RETURN
GRILLE
FI
L
T
E
R
SIDE RETURN
EXTERNAL FILTER
RACK KIT
(EITHER SIDE)
Possible Upright Upflow
FIL
TER
AIR FLOW
CENTRAL
RETURN
GRILLE
RETURN
DUCT
FI
LT
ER
FILTER
SUPPORT
BRACKET
(Field Supplied)
FILTER
ACCESS
DOOR
Possible Upright Counterflow
Filter Locations
H
ORIZONTAL
I
NSTALLATIONS
Filters must be installed in either the central return register or in
the return air duct work.
S
TARTUP
P
ROCEDURE
& A
DJUSTMENT
Furnace must have a 115 VAC power supply properly connected
and grounded. Proper polarity must be maintained for correct
operation. In addition to the following start-up and adjustment
items, refer to further information in Operational Checks section.