SNVT_pwr_fact_f

Data Length

1

Suggested Data Array Formats

Float

Data Item 1

Measurement

Units

Values Range

Invalid Value

Power Factor

N/A

-1 .. 1

N/A

SNVT_reg_val

Data Length

3

Suggested Data Array Formats

Sint32

Data Item 1

reg_val_value

Measurement

Units

Values Range

Invalid Value

Raw value

Defined by unit field

-2,147,483,638 ..
2,147,483,647

N/A

Data Item 2

reg_val_unit

Measurement

Units

Values Range

Invalid Value

reg_val_unit_t

N/A

0 .. 43

255 (0xFF)(RVU_NUL)

Data Item 3

reg_val_decimals

Measurement

Units

Values Range

Invalid Value

Decimal Place

Digits to Right of
Decimal Point

0 ..7

N/A

SNVT_reg_val_ts

Data Length

9

Suggested Data Array Formats

Sint32

Data Item 1

reg_val_ts_raw

Measurement

Units

Values Range

Invalid Value

Raw Value

-2,147,483,648 ..
2,147,483,647

N/A

Data Item 2

reg_val_ts_unit

Measurement

Units

Values Range

Invalid Value

reg_val_unit_t

N/A

0 .. 43

255 (0xFF)(RVU_NUL)

Data Item 3

reg_val_ts_bits

Measurement

Units

Values Range

Invalid Value

See SNVT tables

See SNVT tables

0 .. 255

N/A

Data Item 4

reg_val_ts_year

Measurement

Units

Values Range

Invalid Value

Year

Year

0 .. 300

N/A

Data Item 5

reg_val_ts_month

Measurement

Units

Values Range

Invalid Value

Month

Month of Year

0 .. 12

N/A

Data Item 6

reg_val_ts_day

Measurement

Units

Values Range

Invalid Value

Day

Day of Month

0 .. 31

N/A

Data Item 7

reg_val_ts_hour

Measurement

Units

Values Range

Invalid Value

Hour

Hour of day

0 .. 23

N/A

Data Item 8

reg_val_ts_min

Measurement

Units

Values Range

Invalid Value

Minutes

Minute of Hour

0 .. 59

N/A

Data Item 9

reg_val_ts_secs

Measurement

Units

Values Range

Invalid Value

Minutes

Minute of Hour

0 .. 59