beautypg.com

FieldServer LonWorks FS-8700-21 User Manual

Page 51

background image

FS-8700-21 LonWorks Manual

Page 51 of 72

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Suggested Data Array Formats

Float

Data Item 1

Measurement

Units

Values Range

Invalid Value

Density

Kilograms per Cubic
Meter (kg/m³)

0 .. 3.40282E38

N/A

SNVT_dev_c_mode

Data Length

1

Suggested Data Array Formats

Byte, Uint16, Float

Data Item 1

Measurement

Units

Values Range

Invalid Value

device_c_mode_t

N/A

0 .. 29

255 (0xFF)(DCM_NUL)

SNVT_earth_pos

Data Length

6

Suggested Data Array Formats

Float

Data Item 1

epos_dir_bits

Measurement

Units

Values Range

Invalid Value

Latitude/Longitude

Direction

0 .. 255

N/A

Data Item 2

epos_lat_degs

Measurement

Units

Values Range

Invalid Value

Latitude degrees

Degrees

1 .. 90

255 (0xFF)

Data Item 3

epos_lat_mins

Measurement

Units

Values Range

Invalid Value

Latitude Minutes

Minutes

1 .. 59.999

Raw:

65,535

(0xFFFF)

Type: 65.535

Data Item 4

epos_long_degs

Measurement

Units

Values Range

Invalid Value

Longitude Degrees

Degrees

1 ..180

255 (0xFF)

Data Item 5

epos_long_mins

Measurement

Units

Values Range

Invalid Value

Longitude Minutes

Minutes

1 .. 59.999

Raw:

65,535

(0xFFFF)

Type: 65.535

Data Item 6

epos_htabv_sea

Measurement

Units

Values Range

Invalid Value

Height Above Sea Level Meters (m)

-3.40282E38

..

3.40282E38

N/A

SNVT_elapsed_tm

Data Length

5

Suggested Data Array Formats

Uint16, Float

Data Item 1

etm_day

Measurement

Units

Values Range

Invalid Value

Days

Days

0 .. 65,534

65,535 (0xFFFF)

Data Item 2

etm_hour

Measurement

Units

Values Range

Invalid Value

Hours

Hours

0 .. 23

N/A

Data Item 3

etm_minute

Measurement

Units

Values Range

Invalid Value

Minutes

Minutes

0 .. 59

N/A

Data Item 4

etm_second

Measurement

Units

Values Range

Invalid Value

Seconds

Seconds

0 .. 59

N/A

Data Item 5

etm_millisecond

Measurement

Units

Values Range

Invalid Value

Milliseconds

Milliseconds

0 .. 999

N/A

SNVT_elec_kwh

Data Length

1

Suggested Data Array Formats

Uint16, Float

Data Item 1

Measurement

Units

Values Range

Invalid Value

Electrical energy

Kilowatt-hours

0 .. 65,535

N/A

SNVT_elec_kwh_l

Data Length

1

Suggested Data Array Formats

Sint32

Data Item 1