Appendix B.4. Honeywell Care

This system uses unacknowledged service as default. This protocol driver requires acknowledged service to
operate correctly.

Appendix B.5. CARE and LON PT link Integration

The procedure that follows describes a successful integration from a LonPtLink using Honeywell Care ver 7.0.

Set the PT Link configuration file as follows for LonWorks: Implicit, Update, Update.

Open the device library in Care and create a new Lon device as shown in the example below.

Connect to the Lon side of the PT Link using the Lon network interface cable and set Care to Onnet.