SNVT_press_p

Data Length

1

Suggested Data Array Formats

Sint16, Float

Data Item 1

Measurement

Units

Values Range

Invalid Value

Pressure (gauge)

Pascals

-32,768 .. 32,766

32,767 (0x7FFF)

SNVT_privacyzone

Data Length

3

Suggested Data Array Formats

Uint16, Float

Data Item 1

priv_zn_action

Measurement

Units

Values Range

Invalid Value

privacyzone_t

N/A

0 .. 5

255 (0xFF)(PZ_NUL)

Data Item 2

priv_zn_number

Measurement

Units

Values Range

Invalid Value

Zone number

Privacy zone number

1 .. 255

0

Data Item 3

priv_zn_camera_id

Measurement

Units

Values Range

Invalid Value

Camera ID

ID number

1 .. 65,535

0

SNVT_ptz

Data Length

6

Suggested Data Array Formats

Float

Data Item 1

ptz_pan_dir

Measurement

Units

Values Range

Invalid Value

ptz_pan_dir

Direction

0 .. 255

N/A

Data Item 2

ptz_pan_speed

Measurement

Units

Values Range

Invalid Value

Pan speed

Percent of full level

0.0 .. 100.0

N/A

Data Item 3

ptz_tilt_dir

Measurement

Units

Values Range

Invalid Value

tilt_dir_t

N/A

0 .. 2

255 (0xFF)(TILT_NUL)

Data Item 4

ptz_tilt_speed

Measurement

Units

Values Range

Invalid Value

Tilt speed

Percent of full level

0.0 .. 100.0

N/A

Data Item 5

ptz_zoom

Measurement

Units

Values Range

Invalid Value

zoom_t

N/A

0 .. 2

255 (0xFF)(ZOOM_NUL)

Data Item 6

ptz_zoom_speed

Measurement

Units

Values Range

Invalid Value

ptz_zoom_speed

Meters (m)

-3.40282E38

..

3.40282E38

N/A