Client side map descriptor parameters – FieldServer LonWorks FS-8700-21 User Manual
Page 18
![background image](/manuals/105454/18/background.png)
FS-8700-21 LonWorks Manual
Page 18 of 72
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Example
// Client Side Nodes
Nodes
Node_Name , Subnet_ID , Node_ID , Protocol
LON_1
, 1
, 1
, LonWorks
7.2.3 Client Side Map Descriptor Parameters
7.2.3.1 Driver Related Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch data from or send data to. Needed for
Explicit Addressing.
One of the Node Names
specified in Section 7.2.2
SNVT_Index
Server Network Variable Index
0-4095
SNVT_Type
Standard network variable type of the data
SNVT_Option*
Specifies which record out of a complex SNVT we are after.
SNVT_Units*
Specifies the measurement units if something other than Metric is
required
UNVT_Byte_Length*
Specifies the length in bytes of an UNVT. This Parameter is
compulsory when SNVT_Type is set to UNVT, the parameter is not
used on conjunction with SNVT’s
1-255. See Appendix A.1
UNVT_ID
Specifies the Type Number to apply to this particular UNVT. This
Parameter is optional when SNVT_Type is set to UNVT, The
parameter is not used on conjunction with SNVT’s
0, 146-255. See Appendix
A.1.
NV_Min_Value*
Network Variable updates with values less than specified in this field
will be ignored.
NV_Max_Value*
Network Variable updates with values higher than specified in this
field will be ignored.
NV_Delta_Value*
Network Variable updates where the value’s delta change is less
than specified in this field will be ignored unless the Max_Scan_Time
Condition has been met. Compulsory for Throttling Lon Functions,
not used on other Lon Functions. It is possible to configure a start-
up write option for throttling Map Descriptor functions instead of
waiting for the minimum scan time to pass. Refer to Appendix A.3.
NV_Selfdoc_Text*
The Self-Documenting String for this Network Variable.
Normal Text up to a length
of 40 characters. Defaults to
"" for parameters using
string values and 0 for
parameters using numeric
values
7.2.3.2 Timing Parameters
Column Title
Function
Legal