6.2.4 Client Side Map Descriptor Example

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Lon_Function , Function , Node_Name , SNVT_Type

, Nv_Delta_Value , Min_Scan_Time , Max_Scan_Time , Scan_Interval

TempOut1

, DA_FO_01

, 0

, NVUOIMT

, Wrbc

, LON_1

, SNVT_Temp_f , 10

, 5

, 20

, -

TempOut2

, DA_FO_01

, 1

, NVUOIMX

, Wrbc

, LON_1

, SNVT_Temp_f , -

, -

, -

, -

TempOut3

, DA_FO_01

, 2

, NVUOIMC

, Wrbc

, LON_1

, SNVT_Temp_f , -

, -

, -

, 20

TempIn

, DA_FI_01

, 0

, NVPIIMT

, Rdbc

, LON_1

, SNVT_Temp_f , -

, -

, -

, 5

This field
determines the
Map
Descriptor’s
function. See
Section 6.1.2
for more
information.

Required for Throttling Mode: This field specifies the
minimum change needed for a Network Variable’s
value to invoke an NV Update.

If found during Min_Scan_Time
sampling (Throttling Mode) that
Max_Scan_Time has elapsed since the
last NV Update, a new NV Update will
be transmitted.

For Non-Throttled
Client Map
Descriptors the
Scan_Interval
determines the
update rate.

The Data Array will be
sampled and evaluated for
delta change once every
Min_Scan_Time (seconds)