19 timing chart (logic 2) – IDEC FS1A Controller User Manual
Page 60

5-19
Timing chart (Logic 2)
Safety input : X0
Manual start input
: X16
Safety output :
Y0,Y1,Y2,Y3
Monitor output for
X0 and X1 : Y4
Monitor output for
safety output :
Y12,Y13
RUN monitor :
Y16
Solenoid output :
Y17,Y20
Power ON
Safety output ON
Off delay
time
Safety input : X1
(X2, X4 and X6 are OFF and X3, X5, X7 and
X10...X13 are ON in this timing chart.)
Safety input : X0
Control start input
: X17
Safety output :
Y0,Y1,Y2,Y3
Monitor output for
X0 and X1 : Y4
Monitor output for
safety output :
Y12,Y13
RUN monitor :
Y16
Solenoid output :
Y17,Y20
Power ON
Safety output ON
Off delay
time
Safety input : X1
Min. 0.1s
1.Case to use the manual start input (X16)
2.Case to use the control start input (X17)
0.1s...5s
Max. 6s
Max. 6s
(Note)
Note:
When the input time difference for the dual channel safety inputs is 0.5s or more, an input monitor error is detected.
Refer to the following "Logic functions" for details.
(Note)
Max. 0.1s
(Note)
Max. 0.1s
(Note )
(X2, X4 and X6 are OFF and X3, X5, X7 and
X10...X13 are ON in this timing chart.)
Initialization
Initialization