68 timing chart (logic 7) – IDEC FS1A Controller User Manual
Page 109

5-68
Timing chart (Logic 7)
Safety input : X0
Safety output 1 :
Y0,Y1
Monitor output for
X0 and X1 : Y4
Monitor output for
safety output 1 :
Y12
Solenoid output:
Y17
Power ON
(X4, X5, X10, X11 are ON in this chart.)
Safety input : X2
Safety input :
X6,X7
Control start input
: X12
Safety output 2 :
Y2,Y3
Monitor output for
safety output 2 :
Y13
Solenoid output:
Y20
Safety output 2
ON
Off delay
time
Off delay
time
Safety output
all ON
Safety output
all ON
Manual start input
: X13
Monitor output for
X2 and X3 : Y5
Monitor output for
X6 and X7 : Y7
1. Example to use manual start input (X13) which does not
detect adhesion of the start switch on partial stop.
RUN monitor :
Y16
0.1s...5s
Safety output 1
ON
Off delay
time
Min. 0.1s
Max 6s
0.1s...5s
Safety input : X1
(Note 1)
(Note 1)
Safety input : X3
Note 1: When the input time difference of the dual channel safety inputs is 0.5s or more, an input monitor error is detected.
Refer to the following "Logic functions" for details.
Note 2: Example to turn on the control start input (X12) before turning on the manual start input (X13).
Max. 0.1s
Max. 0.1s
Max. 0.1s
(Note 1)
(Note 1)
Min. 0.1s
Min. 0.1s
Max. 0.1s
(Note 2)
Initialization