PAGE 6 - 27

Chapter 6: System Operation

Specified Point Load Judgment (Method 2 Type 1)

This Load Control press method allows judgment of a load (PS) at a given distance
[13: Target Distance].
Type 1 Control is active if [22: Target Distance] is set to a number other than 0.
Upon start of cycle, the press will operate until it achieves [13: Target Load]. During
the press cycle, checks are performed for “Interference Check” / “Part Check”, Load
and Distance. If any of these values are compromised, the press will stop and return as
programmed.

The Final Judgment will be based upon the load value (PS) at

[22: Judgment Load Detection Point]

.

(See corresponding sections for Interference Check and Part Check explanations.)




ƒ

If “Interference Check” or “Part Check” are not used, set [15: Interference Check

Load / Part Check Load High] and [17: Part Check Load Low] to [10: CAL
Load]
and [23: Interference Check Distance / Part Check Distance] to a
minimum of [21: Distance High Limit].

ƒ

Review Speed Section explanations and cautions when setting [15: Interference

Check Load / Part Check Load High], [14: Press Speed Start Load], [24: Press
Speed Start Distance]
and [20: Approach Distance].








Load

Distance

Max

Load Limit is set to

1.1 x [10] Calibration Load

[11] Load Low Limit

[13] Target Load

[15] Part Check Load High

(Interference Check Load)

[17] Part Check Load Low

[20]

Distance

Low Limit

[21]

Distance

High Limit

[23]

Part Check Distance

(Interference Check Distance)

Part Check - High

(Interference Zone)

Final Judgment Zone

[22]

Judgment Load
Detection Point

Judgment Load (PS)

[12] Load High Limit

Part Check - Low