Chapter 6: System Operation
♦
Load Control (Method 0)
Upon start of cycle, the press will operate until it achieves [13: Target Load]. During
the press cycle, checks are performed for “Interference Check” / “Part Check”, Load
and Distance. If any of these values are compromised, the press will stop and return as
programmed.
(See corresponding sections for Interference Check and Part Check explanations.)
If “Interference Check” or “Part Check” are not used, set [15: Interference Check
Load / Part Check Load High] and [17: Part Check Load Low] to [10: CAL
Load] and [23: Interference Check Distance / Part Check Distance] to a
minimum of [21: Distance High Limit].
Review Speed Section explanations and cautions when setting [15: Interference
Check Load / Part Check Load High], [14: Press Speed Start Load], [24: Press
Speed Start Distance] and [20: Approach Distance].
Load
Distance
[12]
Load High Limit
[13] Target Load
[11] Load Low Limit
[15] Part Check Load High
(Interference Check Load)
[17] Part Check Load Low
[20]
Distance
Low Limit
[21]
Distance
High Limit
Part Check - High
(Interference Zone)
Final Judgment Zone
[23]
Part Check Distance
(Interference Check Distance)
Press Methods
Part Check - Low