Honeywell RAPID EYE K9696V2 User Manual
Page 66
Multi-Media Unit: Installation Instructions
5–8
Table 14
Sensor hardware
Acronym Sensor
Input
Implication
NO
Normally Open
input is active when switch goes ON
NC
Normally Closed
input is active when switch goes OFF
EOL
End of Line
input is active when switch goes ON, or if
wires to the alarm sensor are cut
5.7 Control
Outputs
Purpose
A View operator can activate outputs.
Up to 24 mA can be drawn at each output.
Cable
Use hookup wire in the 20-gauge range to connect the outputs to relay triggered devices
(locks, gates, warning sirens and so on) to a Multi-Media unit.
Tools
You may need:
•
a slot screwdriver—supplied. The screws are slightly smaller than those for a
1/8" screwdriver.
•
a wire stripper.
Connector
1.
From the hookup wires’ tips, strip approximately 0.6 cm (1/4 inch) of insulation.
2.
Insert each relay control wire to the screw-type, terminal connector on the
CONTROL OUTPUTS terminal strip: one wire to ground and the other wire to
the numbered connection you choose.
To avoid short-circuits, ensure that bare wire is not visible at the rear panel.
5.8 System
Monitoring
Fault relay
A Multi-Media unit can be monitored for failure:
•
to function
•
to report alarms
Should such a failure last more than 19 minutes, the FAULT RELAY is triggered.