ProSoft Technology MVI56-DFCMR User Manual
Page 97
Reference MVI56-DFCMR
♦ ControlLogix Platform
DF1 Interface Module with Reduced Data Block
ProSoft Technology, Inc.
Page 97 of 113
October 20, 2008
Function Code #509 - Protected Typed Logical Write (Two Address Fields)
Column
Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled, 1=Continuous and 2=Conditional.
2
Virtual Database Address
This parameter defines the database address of the
first data point to be associated with the command.
3
Poll Interval
Minimum time in tenths of a second to wait before
polling with this command.
4
Count
Number of data word values to be considered by the
function.
5
Swap Type Code
Swap type code for command: 0=None, 1=Swap
words, 2=Swap words & bytes and 3=swap bytes in
each word.
6
Node Address
Address of unit to reach on the data highway.
7
Function Code = 509
Logical Write Command
8
File Type
SLC file type letter as used in file name string. Valid
values for the system are N, S, F, A, ….
P1
9
File Number
SLC file number to be associated with the command.
P2
10
Element Number
The parameter defines the element in the file where
write operation will start.
P3
11
Not Used
This field is not used by the command. Values entered
in this column will be ignored.
P4
This function writes one or more words of data to a PLC data table.
Function Code #510 - Protected Typed Logical Write (Three Address Fields)
Column
Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled, 1=Continuous and 2=Conditional.
2
Virtual Database Address
This parameter defines the database address of the first
data point to be associated with the command.
3
Poll Interval
Minimum time in tenths of a second to wait before
polling with this command.
4
Count
Number of data word values to be considered by the
function.
5
Swap Type Code
Swap type code for command: 0=None, 1=Swap words,
2=Swap words & bytes and 3=swap bytes in each word.
6
Node Address
Address of unit to reach on the data highway.
7
Function Code = 510
Logical Write Command
8
File Type
SLC file type letter as used in file name string. Valid
values for the system are N, S, F, A, ….
P1
9
File Number
SLC file number to be associated with the command.
P2
10
Element Number
The parameter defines the element in the file where
write operation will start.
P3
11
Sub-Element Number
This parameter defines the sub-element to be used with
the command. Refer to the AB documentation for a list
of valid sub-element codes.
P4
This function writes one or more words of data to a PLC data table. This function
should work on the following devices: SLC 500, SLC 5/03 and SLC 5/04.