Diagnostics and Troubleshooting

MVI56-DFCMR ♦ ControlLogix Platform

DF1 Interface Module with Reduced Data Block

ProSoft Technology, Inc.

Page 61 of 113

October 20, 2008

The bits in each configuration word are shown below. The module configuration
error word has the following definition:

Bit Description

Value

0

Read block start value is greater than the database size.

0x0001

1

Read block start value is less than zero.

0x0002

2

Read block count value is less than zero.

0x0004

3

Read block count + start is greater than the database size.

0x0008

4

Write block start value is greater that the database size.

0x0010

5

Write block start value is less than zero.

0x0020

6

Write block count value is less than zero.

0x0040

7

Write block count + start is greater than the database size.

0x0080

8

0x0100

9

0x0200

10

0x0400

11

0x0800

12

0x1000

13

0x2000

14

0x4000

15

0x8000

The port configuration error words have the following definitions:

Bit Description

Value

0

Type code is not valid. Enter a value from 0 (master) to 1 (slave). 0x0001

1

Protocol parameter is not valid.

0x0002

2

Termination type parameter is not valid.

0x0004

3

Baud rate parameter is not valid.

0x0008

4

Parity parameter is not valid.

0x0010

5

Data bits parameter is not valid.

0x0020

6

Stop bits parameter is not valid.

0x0040

7

Command count parameter is not valid.

0x0080

8

Retry count parameter is not valid.

0x0100

9 Spare

0x0200

10

Spare

0x0400

11 Spare

0x0800

12

Spare

0x1000

13 Spare

0x2000

14

Spare

0x4000

15 Spare

0x8000

Correct any invalid data in the configuration for proper module operation. When
the configuration contains a valid parameter set, all the bits in the configuration
words will be clear. This does not indicate that the configuration is valid for the
user application. Make sure each parameter is set correctly for the specific
application.