MVI56-DFCMR ♦ ControlLogix Platform
Installing and Configuring the Module
DF1 Interface Module with Reduced Data Block
Page 30 of 113
ProSoft Technology, Inc.
October 20, 2008
Register Content
Description
5034 File
Offset
This parameter sets the database register location of
the first element in the first file simulated in the
module. All offsets in the first file and subsequent
files will be computed using the address specified.
This value is fixed at 0. Therefore, the module
assumes N7:0 starts at the database offset of 0 and
each file is 200 words in size.
5035
Map Count
Number of file map overrides.
5036 to 5039
Spare
2.2.3 Port 2 Setup
Register Content
Description
5040 Enable
This parameter is used to define if this port will be
utilized. If the parameter is set to 0, the port is
disabled. A value of 1 will enable the port.
5041 Type
This parameter defines if the port will emulate a
master or slave device. Enter 0 to emulate a master
device and 1 to emulate a slave device.
5042
Local Station ID
This parameter specifies the local station ID for all
DF1 messages sent from this master port. A value of
255 is not permitted as this is the broadcast address.
Enter a value in the range of 0 to 254.
5043
Protocol
0=full duplex, 1=half-duplex
5044 Termination
Type
This parameter specifies the error checking for all
DF1 messages. 0=BCC, 1=CRC
5045 Baud
Rate
This is the baud rate to be used on the port. Enter
the baud rate as a value.
Baud Rate
Parameter Value
110
110
150
150
300
300
600
600
1200
12 or 1200
2400
24 or 2400
4800
48 or 4800
9600
96 or 9600
14,400
14, 114 or 14400
19,200
19, 192 or 19200
28,800
28, 288 or 28800
38,400
38, 384 or 38400
57,600
57 or 576
115,200
115 or 1152
5046 Parity
This is the Parity code to be used for the port. The
coded values are as follows: 0=None, 1=Odd,
2=Even.