Led status indicators, E 60), Status – ProSoft Technology MVI56-DFCMR User Manual
Page 60: Indicators
MVI56-DFCMR ♦ ControlLogix Platform
Diagnostics and Troubleshooting
DF1 Interface Module with Reduced Data Block
Page 60 of 113
ProSoft Technology, Inc.
October 20, 2008
4.2
LED Status Indicators
The LEDs indicate the module's operating status as follows:
Module Color
Status
Indication
On
Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.
CFG Green
Off
No data is being transferred on the Configuration/Debug port.
On
Data is being transferred between the module and the DF1
network on Port 1.
P1 Green
Off
No data is being transferred on the port.
On
Data is being transferred between the module and the DF1
network on Port 2.
P2 Green
Off
No data is being transferred on the port.
On
The MVI56-DFCMR is working normally.
APP Amber
Off
The MVI56-DFCMR module program has recognized a
communication error on one of its ports.
On
The LED is on when the module is performing a write
operation on the backplane.
BP ACT
Amber
Off
The LED is off when the module is performing a read
operation on the backplane. Under normal operation, the LED
should blink rapidly on and off.
Off
The card is not receiving any power and is not securely
plugged into the rack.
Green
The module is operating normally.
OK
Red /
Green
Red
The program has detected an error or is being configured. If
the LED remains red for over 10 seconds, the program has
probably halted. Remove the card from the rack and re-insert
the card to restart the module's program.
Off
The battery voltage is OK and functioning.
BAT Red
On
The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.
During module configuration, the OK will be red and the APP and BP ACT LEDs
are on.
If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this
indicates a serious problem with the module. Call ProSoft Technology support to
arrange for repairs.
If the LEDs are latched in this mode for a long period of time, look at the
configuration error words in the configuration request block. The structure of the
block is shown in the following table.
Offset Description
Length
0 Reserved
1
1 9000
1
2
Module Configuration Errors
1
3
Port 1 Configuration Errors
1
4
Port 2 Configuration Errors
1
5 to 40
Spare
36
41
-2 or -3
1