ProSoft Technology MVI69-DNP User Manual
Page 88
MVI69-DNP ♦ CompactLogix or MicroLogix Platform
Reference
DNP 3.0 Master/Slave Communication Module
Page 88 of 129
ProSoft Technology, Inc.
November 3, 2008
Review the Installing and Configuring the Module section for a complete list of
parameters that must be defined for a slave port. The response messages from
the slave driver include an IIN (internal indication word) defined in the Reference
chapter - Internal Indication Word.
The slave driver supports Object 110 (octet string data). Four points are pre-
assigned values as shown in the following table.
OCTET STRING POINT LIST
Point #
Description
0
Module Name as assigned in configuration file.
1 Product
Name
2
Version Information in format:
wwww xxxx yyyy zzzz
Where wwww is product code, xxxx is the revision, yyyy is the operating
system number and zzzz is the run number.
3
Manufacturer name for module.
Master Driver Mode
In the Master mode, the MVI69-DNP module is responsible for issuing read or
write commands to slave devices on the DNP network. These commands are
user-configured in the module via the Master Command List received from the
processor or issued directly from the processor (command control). Command
status is returned to the processor for each individual command in the command
list status block. The following flow chart and associated table describe the flow
of data into and out of the module.